IPC [bdsm]¶
If you are using
- Frame format. All communication should be enveloped in following frame format:
|B|D|S|M|<LB>|<LE>|<DATA>|<C>|
Where <L> is two byte field in BE that contains length of <DATA>, <C> is checksum of <DATA> (sum of all bytes modulo 256). BDSM(Bobaos Datapoint Sdk Message) is a string header of message.
<DATA> field description¶
Field <DATA> is stringified JSON object which shoud match next format in case of Client => Host communication:
{
request_id: Number,
method: String,
payload: Object // optional
}
Fields explanation¶
request_id
¶
field should be unique at the moment of sending and it is responsibility of client to process this value. Server sends responses with this value in response_id field back to client.
method
field.¶
get datapoints
¶
Get all configured datapoint descriptions.
Request:
{"request_id":18052831966,"method":"get datapoints"}
Response:
{"response_id":18052831966,"method":"get datapoints","payload":[{"id":1,"length":1,"flags":{"priority":"low","communication":true,"read":false,"write":true,"readOnInit":false,"transmit":true,"update":false},"dpt":"dpt1"},{"id":2,"length":1,"...}]}
get description
¶
Get description for datapoint with specified id.
Request:
{"request_id":145663188249,"method":"get description","payload":{"id":31}}
Response:
{"response_id":145663188249,"method":"get description","payload":{"id":31,"value":{"id":31,"dpt":"dpt5","flags":{"priority":"low","communication":true,"read":false,"write":true,"readOnInit":false,"transmit":true,"update":false},"length":1}},"success":true}
get value
¶
Get datapoint value.
Request:
{"request_id":65362052157,"method":"get value","payload":{"id":31}}
Response:
{"response_id":65362052157,"method":"get value","payload":{"id":31,"value":74},"success":true}
read value
¶
Send read request to KNX bus.
Request:
{"request_id":611387384802,"method":"read value","payload":{"id":31}}
Response:
{"response_id":611387384802,"method":"read value","payload":{"id":31},"success":true}
set value
¶
Set datapoint value and send to KNX bus.
Request:
{"request_id":839768583900,"method":"set value","payload":{"id":31,"value":5}}
Response:
{"response_id":839768583900,"method":"set value","payload":{"id":31},"success":true}
programming mode
¶
Set programming mode. As if you press PROG button.
Request:
{"request_id":1366287859749,"method":"programming mode","payload":{"value":1}}
Response:
{"response_id":1366287859749,"method":"programming mode","success":true}
get stored value
¶
Get datapoint value, stored in bdsd.sock process. Use it if you want to avoid unnecessary serialport communication to retreive datapoint value.
Request:
{"request_id":65362052157,"method":"get stored value","payload":{"id":31}}
Response:
{"response_id":65362052157,"method":"get stored value","payload":{"id":31,"value":74},"success":true}
read multiple
¶
Read multiple datapoints.
Request:
{"request_id":175279505890,"method":"read multiple","payload":[1,105,106,107,108]}
Response:
{"response_id":175279505890,"method":"read multiple","payload":[1,105,106,107,108],"success":true}
set multiple
¶
Set multiple datapoints
Request:
{"request_id":1526404778316,"method":"set multiple","payload":[{"id":2,"value":false},{"id":999,"value":"hello, drug"}]}
Response:
{"response_id":1526404778316,"method":"set multiple","payload":[{"id":2,"value":false},{"id":999,"value":"hello, drug"}],"success":true}
Broadcasting value.¶
When datapoint value changes on bus, socket broadcasts following data to all connected clients:
{"method":"cast value","payload":{"id":12,"value":22.92}}
Notify¶
When Client connects to socket, initial notification sends from Host to Client indicating connectino status:
{"method":"notify","payload":"bus connected"}
Error handling¶
In case of error Host sends to Client data with “success” field set to false and error message in “error” field.
Request:
{"request_id":289551154644,"method":"set value","payload":{"id":31,"value":257}}
Response: